Refrigeration System Section 7
7-20
Part Number 80-1634-3
Cycle Time/24 Hour Ice Production/
Refrigerant Pressure Charts
These charts are used as guidelines to verify correct ice
machine operation.
Accurate collection of data is essential to obtain the
correct diagnosis.
Refer to “OPERATIONAL ANALYSIS TABLE” for the
list of data that must be collected for refrigeration
diagnostics. This list includes: before beginning
service, ice production check, installation/visual
inspection, water system checklist, ice formation
pattern, safety limits, comparing evaporator inlet/
outlet temperatures, discharge and suction pressure
analysis.
Ice production checks that are within 10% of the
chart are considered normal. This is due to variances
in water and air temperature. Actual temperatures
will seldom match the chart exactly.
Zero out manifold gauge set before obtaining
pressure readings to avoid misdiagnosis.
Discharge and suction pressure are highest at the
beginning of the cycle. Suction pressure will drop
throughout the cycle. Verify the pressures are within
the range indicated.
Record beginning of freeze cycle suction pressure
one minute after water pump energizes.
Regular cube production derate is 7%
50Hz production derate is 7%
50Hz regular cube total production derate is 14%
S1800 SERIES
Self-Contained Water-Cooled
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
24 Hour Ice Production
Operating Pressures
Air Temp.
Around Ice
Machine
°F/°C
Freeze Time
Harvest
Time
Water Temperature °F/°C
50/10.0 70/21.1 90/32.2
70/21.1 8.5-9.4 9.2-10.1 10.7-11.8
.75-2.00
80/26.7 8.5-9.4 9.3-10.3 10.9-12.0
90/32.2 8.6-9.4 9.4-10.4 11.1-12.2
100/37.8 8.7-9.6 9.6-10.5 11.2-12.3
Times in minutes
Air Temp.
Around Ice
Machine
°F/°C
Water Temperature °F/°C
50/10.0 70/21.1 90/32.2
70/21.1 1870 1750 1530
80/26.7 1870 1730 1510
90/32.2 1860 1710 1490
100/37.8 1830 1690 1470
Based on average ice slab weight of 13- 14.125 lb
Condenser
Water
Consumption
Air Temperature / Water Temperature °F
77/59 90/70 110/90
Gal / per
100 lbs of ice
95 155 510
Water regulating valve set to maintain 240 PSIG discharge pressure
Air Temp.
Around Ice
Machine
°F/°C
Freeze Cycle Harvest Cycle
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
50/10.0
225-235 40-24 140-160 60-80
70/21.1 225-275 45-26 155-175 60-85
80/26.7 230-295 45-28 160-180 70-90
90/32.2 255-320 46-29 170-195 80-100
100/37.8 290-360 48-30 190-215 95-115
110/43.3 325-400 49-30 225-250 110-130
Suction pressure drops gradually throughout the freeze cycle