Section 2 Installation Instructions
Part Number 000001530 2-7
Electrical Requirements
QUIETQUBE® ICE MACHINE HEAD SECTION
CVD® CONDENSING UNIT
CONNECT POWER SUPPLY WIRING DIRECTLY TO L1 & L2 ON THE CONTACTOR.
TORQUE SCREWS TO THE TORQUE VALUE SPECIFICATION ON THE CONTACTOR LABEL.
FOLLOW ALL LOCAL, STATE AND NATIONAL ELECTRICAL CODES.
Ice Machine
Voltage
Phase
Cycle
Maximum Fuse/
Circuit Breaker
Total Amps
QDUALC
115/1/60
208-230/1/60
230/1/50
15 amp
15 amp
15 amp
1.1
0.6
0.6
Important
The QuietQube® Ice Machine Head Section and
CVD Condensing Unit are wired independently from
each other.
Condensing Unit
Voltage Phase
Cycle
Maximum Fuse/
Circuit Breaker
Minimum Circuit
Amps
Minimum Wire Size To
Condensing Unit
CVD1875
208-230/1/60
40 24.3 8 AWG
208-230/3/60
30 16.1 8 AWG
230/1/50 40 23.2 8 AWG
CVD2075
208-230/1/60 50 27.1 8 AWG
208-230/3/60 40 19.9 8 AWG
230/1/50 50 29.9 8 AWG